First Step - We need to know the total cooling capacity of AHU or FCU.
Let's say , Total Cooling Capacity of FCU is 22kW and Total Cooling Capacity of AHU is 250kW.
Second Step - We need to calculate the chilled water flow rate.
Based on Sensible Heat Equation : q = m c ΔT
q = total cooling capacity of AHU or FCU or Chiller (kW)
c = specific heat capacity of water ( 4.19 kJ/kgK)
ΔT = Chilled water supply temp and chilled water return temp (K) . (Normally Ts- 6.7C and Tr- 12.2C)
m = Chilled water flow (kg/s) For Water (kg/s = l/s) Since density of water is 1000 kg/m3.
For FCU - 22 kW ,
Chilled Water Flow Rate = q / ( c ΔT) = 22 / (4.19 x 5.5)
So chilled water flow rate for FCU (22-kW) is 0.955 l/s (kg/s).
For Chilled Water Piping ,As per ASHRAE Guideline; Less than or equal of 50mm Pipe size ,
Water Velocity shall be less than 1.2 m/s .
Normally we design 1 m/s for less than or equal 50mm pipe size .
Based on Continuity Equation Q = A V
Q = Volumetric Flow Rate (m3/s)
A = Area ( m2 )
V = Average Water Velocity (m/s)
A = Q / V = 0.955 x 10^-3 / 1
A = 955 mm2
r = 17.4 mm ( A = π r2 )
D = 34.8 mm , Nominal Diameter is 32mm and Actual inside diameter of 32mm is 35mm.
So that chilled water pipe size for FCU (22kW) is 32mm.
For AHU (250 kW) ,
q = mc ΔT
m = Q = q/ c ΔT = 250 / (4.19 x 5.5 ) = 10.85 l/s ( kg/s)
Q = 10.85 l/s .
For AHU Chilled Water Pipe size , As per ASHRAE Guideline ,
Water Pressure Drop Shall be not more than 400 Pa/meter run.
Most of the project design are using 250 Pa/m
Water Velocity shall be less than 2.4 m/s
Based on Flow Rate - 10.85 l/s and not more than 250 Pa/m , Pipe size shall be 100mm.
If we choose pipe size 100mm, Water Pressure drop shall be 175 Pa/m and
Water Velocity shall be 1.32 m/s .
Thanks a lot.
Zaw Moe Khine
RSED Engineering.