Sample Heat Load Calculation for General Office Meeting Room

Sample Heat Load Calculation for General Office Meeting Room


Heat Load Calculation -
-Cooling Capacity (kW) ,
-Supply Air Volume (CMH),
-Supply Fresh Air Volume (CMH),
-Chilled Water Flow Rate (l/s) if CHW System is used. 


When we calculate the heat load,
We need some information for space.
1-Location of space
(Ambient Temp for out door air )
(Singapore -Summer Ambient Temp - 32.8C/26.1C (DB/WB)
2- Room/ Space Datas & Orientation (Facade Orientation)
(Area-50 m2  & Room is located at North Side of Building)
3-Room Construction Materials
(Such as Window Glass (U-value & Sc-Value) ,Wall, Partition & Floor.)
4-No of Occupancy & Room Usage
(20-Persons & Meeting Room)

I-Internal Heat Gain
i-Heat Gain from Lighting 
 (Based on SS-530-Office Lighting Power - 15 W/m2)
 Lighting Load = 50 x 15 = 750 W
ii-Heat Gain from Human (20-person)
 (Based on ASHRAE Office Human Sensible -75 W/person & Latent 55 W/person)
Human Load (S) 75 x 20 = 1500 W ,(L) 55 x 20 = 1100 W
iii-Electrical Equipments Load ( General Office 25 W/m2)
Laptop-55 W x 20 & Projector-300 W.
Electrical Equipments Load= 30 x 50 = 1500 W
II-External Heat Gain 
 i-Heat Gain from Wall (Conduction Heat Gain)
 (Q= A x U x ∆T)
Wall Area = 10 m x 1m = 10m2
Wall U-value(200mm brick wall = 2.254 W/m2) 
∆T for North side facing 200mm brick wall = 14
So, Q= 10 x 2.254 x 14 =  315.56 W
 ii- Heat Gain from Glass Window. (Conduction + Radiation Heat Gain)
 Glass Area = 10 m x 3 m = 30m2
 Glass U-value = 1.7 W/m2
 Glass Sc-Value = 0.3 
 CF = 0.8
(Q= (3.4 x A x U ) + (211 x A x Sc x CF)
 Q = (3.4 x 30 x 1.7 ) + (211 x 30 x 0.3 x 0.8 ) = 1692.6 W
iii- Heat Gain from Partition Wall ( Conduction Heat Gain)
 (Q= A x U x ∆T)
  Partition Area = 20 x 4 = 80 m2
  Partition Wall U-Value = 0.573 W/m2
  ∆T (30-24) = 6
 Q = 80 x 0.573 x 6 = 275 .04 W

iv- Heat Gain from Floor ( Conduction Heat Gain)
 (Q= A x U x ∆T)
  Floor Area = 50 m2
  Floor U-Value = 2.452 W/m2
  ∆T (30-24) = 6
 Q = 50 x 2.452 x 6 = 735.6 W
After adding out the total heat load- 
Sensible Heat Load is 6746.8 W (10% SF) 7421.53 W = 7.421 kW.
Latent Heat Load is 1100 W (10% SF)-1210 W =1.21 kW
SHR = SH/(SH+LH) = 7.421/(7.421+1.21) = 0.86
That's mean 86% is Sensible and 14 % is Latent heat.  
 Once we get the total sensible heat load, we can get the supply air volume.
Qs = m c  ∆T 
 Qs = 7.421 kW (kJ/s)
 c = 1.004 kJ/kg
If supply air temp is 14 C, ∆T = 24-14 = 10.
m = Qs / (c x ∆T)     - (kg/s)
m = 7.421 / (1.004 x 10 ) = 0.73919 kg/s
V,Air Volume (m3/s) = m x v  (Humid Volume-m3/kg)
If supply air temp is 14 C, v is about 0.825 m3/kg.
So, Air Volume , V = 0.73919 (kg/s) x 0.825 (m3/kg)
                       V = 0.6098 m3/s = 2195 CMH.
So, Supply Air Volume is 2195 CMH.
  
Next step is Fresh Air Volume Supply, If the space type is under office,
Minimum FA Requirement is based on 62.1 ASHRAE 
(2.5 l/s/person + 0.3 l/s/m2)= (2.5x20) + (0.3x50)=65 l/s
Minimum FA Requirement based on local code (SS-553).
5.5 l/s/person or 0.6 l/s/m2 (Choose higher volume)
5.5 x 20 = 110 l/s.
So, We have to choose 110 l/s for this meeting room.
Fresh Air Supply will be 110 l/s (396 CMH).


Air Con Sketch





   






















So,supply air volume 2195 cmh & fresh air volume-396 cmh for this meeting room.
Layout will be as per air con sketch. Just need to calculate how much capacity we need.
For Cooling Load Capacity ,
 Q = m ∆h 
 m = mass of air (kg/s) (we already calculated)
∆h = enthalpy differential of entering air and leaving  air (kJ/kg)

For  ∆h = h1-h2 
h1= enthalpy of entering air into coil (maxing air)
h2= enthalpy of leaving air from coil (supply air)
So that we need to calculate maxing air temp.
Mixing air volume is same as supply air volume. See Air con Sketch dwg. 
 In our design condition,
Supply Air Temp is 14 C & Room Operation Temp is 24C(maxi) & RH is 50~55 %.
Fresh air temp is Singapore Summer Temp , 32.8 C (DB) & 26.1 C (WB).
So that we can calculate maxing air temp (entering air temp/on coil air temp).
Supply air volume (maxing air volume) is addition of return air  volume and fresh air volume. So, maxing air temp is depended on ratio of return and fresh air volume.

Equation will be -
Tm x Mixing Air Volume = (Tr x Return Air Volume) + (Tf x Fresh Air Volume) 
Other way is
Tm x 100% = (Tr x Return Air % of Supply Air) + (Tf x Fresh Air % of Supply)
So we just calculate fresh air volume % of supply air volume = 396 / 2195 x 100 = 18%
Fresh air volume is 18%, return air volume will be 100-18= 82%.

Tm x 100 = ( Tr x 82) + (Tf x 18)
Tr = Room Operation Temp (24 C)
 (It should add 1 or 2 C for duct heat gain and plenum heat gain)
Tf = Fresh Air Temp (32.8 C).
Tm x 100 = (24x82) + (32.8 x 18)
Tm =  25.58 C
Mixing Air Temp (DB) is 25.58 C.
Next step is maxing air temp (WB ) or Humidity Ratio (∆g)
Same as maxing air temp (DB)- 
equation will be  
gm x Mixing Air Volume = (gr x Return Air Volume) + (gf x Fresh Air Volume)  
gm x 100 = ( gr x 82) + (gf x 18)  
gr = Return Air Humidity Ratio
Read from Psychrometric Chart  by Room Operation Temp ( 24 C & RH-54%)
gr=9.8 g/kg = 0.0098 kg/kg
gf = Fresh Air Humidity Ratio. 
Read from Psychrometric Chart  by Singapore Summer Temp ( 32.8 C & 26.1 C)
gf = 18.6 g/kg = 0.0186 kg/kg.
So gmx100 = (0.0098 x 82)+(0.0186x18)
gm = 11.83 g/kg = 0.01183  kg/kg

By Maxing Air Temp (DB) Tm,25.58C & Mixing Air Humidity Ratio (gm) 11.83 g/kg,
h1=55 kJ/kg (From Psychrometric Chart)

For h2, Read from Psychrometric Chart
Based on supply air temp,coil ADP,Space SHR & intersection line.
Supply Air temp is 14 C.
Space SHR = 0.86
Coil ADP = 12.71 C (By coil bypass factor is 0.1) 
h2= 37.2 kJ/kg.
So, Cooling Capacity is
Q = m ∆h   
m = 7.421 / (1.004 x 10 ) = 0.73919 kg/s
∆h = h1-h2 = 55- 37.2 = 17.8 kJ/kg
Q = 0.73919 x 17.8
Q =  13.15 kJ/s (kW) 
Fan Coil Unit minimum cooling capacity is 13.15 kW.
Cooling Rate is 13.15/50x100 = 263 W/m2.
Supply Air Volume is 2195 CMH
Fresh Air Volume is 396 CMH.

If FCU is chilled water system and  CHW T is 5.5,
Chilled Water Flow rate ?
Q = m c ∆T
Q = V c ΔT

Q = Cooling Capacity (kJ/s) (kW)
V = Water Flow (m3/s)
ℓ = Density of water (kg/m3) (1000 kg/m3 for water)
c = Specific Heat Capacity of Water (4.19 kJ/kg)
m= mass of water (kg/s)
∆T = 5.5 
V = Q / c ∆T = 13.15 / (1000x4.19 x 5.5) 
V = 0.00057 m3/s
(1m3/s = 1000 l/s)
So, V =  0.57 l/s.
So Chilled Water Flow Rate is 0.57 l/s. 
So that for CHW System, m = V = .... (Unit is l/s)

Q = m c ∆T
m = Q / (c x ∆T) ... (l/s)

   
Thanks,
zaw moe khine 








 



13 January 2013

HEAT LOAD CALCULATION

When we calculate the heat load, we have to know the location of space (Country,City)
And then building information such as building type,material,orientation & authority standard (Which standard we have to follow? local or international ).
Main Heat Source are Internal Heat Gain , External Heat Gain and Heat Gain from OA (FA)
See following Heat Load Chart.


1-Internal Heat Gain
  • Heat Gain from Lighting 
  • Heat Gain from Human
  • Heat Gain from Electrical Equipments
2-External Heat Gain
  •  Heat Gain from Wall 
  •  Heat Gain from Window
  •  Heat Gain from Roof
  •  Heat Gain from Floor
  •  Heat Gain from Partition
3-Heat Gain from Outdoor Air /Fresh Air 
  •   Fresh Air Requirement for Comfort Air
  •   Fresh Air by infiltration  









How to size the chilled water pipe for AHU and FCU? First Step -  We need to know the total cooling capacity of AHU or FCU.  Let's s...